Reference:
          
       	  
            FHSD8015-09  
          
      
      
      
      
      
       
         
      
      
        Smoke detector by suction LaserSense Micra 10 with laser camera for early detection. Dynamic  0,0015% to  25% range of  darkening/metre. 1 piping input up to 50 m. maximum. ClassiFire algorithm for dynamic adjustment of functional parameters (dirt, environment, etc). LDD 3D3 technology, for dirt adjustments in laser camera. 4 alarm levels (Aux, Pre-alarm, Alarm 1 y Alarm 2). Maximum number of sampling points 10 in class C, 6 in class B y 2 in class A. 2 relay outputs (Alarm and breakout). Requires 24V power supply (350mA). Optional aditional Input and output card. Measures: 1145x220x85mm. Certificates: CE and CPR (EN54 part 20).
         
      	
	  
      
	
      
    
 
  